RPZ test procedure, step by step.

Reduced-pressure principle backflow assembly (RPBA). Relief valve opens at 2.0 psid or more. #1 check holds 5.0 psid or more, above the relief opening. #2 check is tight against backpressure.

Last updated .

Before you test: N.I.I.O.

Notify, Identify, Inspect and Observe, in that order, before a hose goes on.

Notify

On an RPZ:

Identify

On an RPZ:

Inspect

On an RPZ:

Observe

On an RPZ:

TC is a test cock. SOV is a shut-off valve. psid is pounds per square inch, differential.

Pressurizing the gauge

  1. FLUSH test cocks: open #4 TC and establish flow, then open TCs #3, #2, #1. Then close TCs #1, #2, #3 and #4.
  2. ATTACH the high side hose to the #2 TC.
  3. ATTACH the low side hose to the #3 TC.
  4. PRESSURIZE the low side of the gauge by opening the #3 TC. Open the low bleed needle valve and let it flow.
  5. PRESSURIZE the high side of the gauge by opening the #2 TC slowly. Open the high bleed needle valve and let it flow.
  6. CLOSE shut-off #2.
  7. CLOSE the high bleed needle valve, and allow the gauge reading to rise to the upper end of the scale.
  8. CLOSE the low bleed needle valve.
  9. OBSERVE whether the gauge reading remains above the relief valve opening point. Note it as the apparent differential pressure across the #1 check.
    • If the gauge reading drops to the low end of the scale and the relief valve discharges continuously, the #1 check is leaking. The rest of the test can't be completed.

Relief valve test

The relief valve must open before the differential pressure across check #1 is less than 2 psid.

  1. OPEN the high side control needle valve at least one full turn.
  2. OPEN the low side control needle valve slightly, no more than ¼ turn. This transfers pressure from the high side of the gauge into the zone of reduced pressure, to purposely equalize the differential pressure across the #1 check.
  3. OBSERVE the gauge as it slowly descends to the relief valve opening point. Record the opening point when the first discharge of water is detected. Must be 2 psid or greater.
    • If the gauge drops below 2 psid and then the relief opens, or the gauge descends to zero and the relief doesn't open at all, record the relief valve as failing, but continue the test.
    • If the low control needle valve is opened a quarter turn and the reading does not decrease to the relief opening, shut-off #2 is leaking. Continuing requires a temporary bypass hose from the #1 TC to the #4 TC.
  4. CLOSE the low control needle valve. Leave the high control needle valve open.

Check valve #2: tightness against backpressure

  1. VENT air from the bypass hose by opening the bypass control needle valve, then close it.
  2. ATTACH the bypass hose to the #4 TC, then open the #4 TC.
  3. OPEN the low bleed needle valve, allowing the gauge needle to rise above the apparent differential pressure across the #1 check. Then close the low bleed needle valve and allow the gauge reading to stabilize.
  4. OPEN the bypass control needle valve. This backpressures the #2 check with pressure from the high side of the gauge. If the gauge remains above the relief valve opening point, record the #2 check as tight on the test report.
    • If the gauge reading descends to steady relief valve opening, open the low bleed needle valve until the gauge rises above the apparent differential pressure across the #1 check, then close it. If the gauge descends to the relief opening point again, record the #2 check as leaking. The rest of the test can't be completed.
    • If the gauge reading stabilizes after closing the low bleed needle valve, record the #2 check as tight (disc compression was present).
    • If the gauge reading rises to the upper end of the scale when the bypass is opened, backpressure may be present. This could allow backflow through the gauge while it is connected. Close the #2 TC.
      • If the gauge reading stops rising or falls to the low end of the scale, it was a false backpressure indication, possibly from a pressure fluctuation. Open the #2 TC and continue the test.
      • If the gauge reading continues to rise with the #2 TC closed, backpressure is present. Close the #4 TC and record the #2 check as tight. Record the apparent differential pressure across the #1 check as actual, because there was no flow with the backpressure present. The relief opening was already recorded. The test is complete.

Check valve #1 test

Record the differential pressure across the #1 check now that the assembly is in a no-flow condition. The reading must be above the relief valve opening point and at least 5.0 psid.

  1. OPEN the low bleed needle valve, allowing the gauge reading to rise above the apparent psid across check #1. Then close the low bleed needle valve and allow the gauge to stabilize. Record the value as the actual differential pressure across the #1 check.
  2. CLOSE the TCs, detach the gauge, slowly restore customer service by slowly opening SOV #2, and complete the test report.

Failure matrix

What can go wrong at each step, what it means, and what goes on the report.

StepYou seeIt meansResultNext
9Gauge drops to the low end and the relief valve discharges continuously#1 check is leaking#1 check failsStop: the rest of the test can't be completed.
12Relief valve opens below 2.0 psidRelief valve opens too lowRelief failsRecord it and continue the test.
12Gauge falls to zero and the relief valve never opensRelief valve stuck, or its sensing line pluggedRelief failsRecord it and continue the test.
12Reading does not drop with the low control needle valve open ¼ turnShut-off #2 is leaking, with flow through the assemblyContinueFit a temporary bypass hose from the #1 TC to the #4 TC, then repeat.
17Gauge descends to the relief opening point, and again after re-bleeding above the apparent #1 reading#2 check is leaking#2 check failsStop: the rest of the test can't be completed.
17Gauge settles and holds after the low bleed needle valve is closedDisc compression#2 check tightContinue to the #1 check test.
17Gauge rises to the top of the scale when the bypass opensBackpressure may be presentCheckClose the #2 TC and watch the gauge.
17…then stops rising, or falls to the low endA pressure fluctuation, not backpressureContinueReopen the #2 TC and continue the test.
17…then keeps rising with the #2 TC closedBackpressure is present, so there is no flow#2 check tightClose the #4 TC. Record the apparent #1 reading as actual. The test is complete.
18#1 check below 5.0 psid, or not above the relief opening point#1 check is weak or fouled#1 check failsRecord the reading; clean or repair and retest.

Troubleshooting an RPBA

Many problems are corrected by cleaning the internal components. Carefully observe the condition of the components. Shut-off valves can be re-opened and closed for a better seal. Use lubricants only to help reassemble components, and only non-toxic ones.

ProblemPossible causes
Relief valve discharges continuouslyFaulty #1 check valve (with no flow)
Faulty #2 check valve with a backpressure condition
Faulty relief valve
Plugged relief valve sensing line(s)
Leak through the relief valve diaphragm
Relief valve discharges intermittentlyA properly working assembly with large pressure fluctuations
#1 check valve reading too close to the relief valve opening point, with a small line pressure fluctuation
Water hammer
#1 check valve leak with intermittent flow through the assembly
Relief valve discharges after #2 shut-off is closed (test #1)Normally a faulty #1 check valve (dirty or damaged disc or seat)
Leak through the relief valve diaphragm
Relief valve would not open; differential on the test kit would not drop (test #1)Leaky #2 shut-off valve with flow through the assembly (requires a temporary bypass hose from the #1 to the #4 TC)
Relief valve would not open; differential drops to zero (test #1)Relief valve stuck (corrosion or scale)
Relief valve sensing line plugged
Relief valve opens too high (with a sufficiently high #1 check reading)Faulty relief valve (dirty or damaged disc or seat)
#1 check valve reading too low: less than 5.0 psid (tests #1 and #3)Dirty or damaged disc or seat
Guide members hanging up
Damaged spring
Leaky #2 check valve (test #2)Dirty or damaged disc
Dirty or damaged seat
Guide members hanging up
Damaged spring